Bem-vindos à SAUTER Ibérica!

 Se você tem dúvidas ou deseja falar com algum especialista, o encaminhamos à pessoa certa!

modu422 -Automation Station

Your advantage for energy efficiency
Local plant data logging enables the analysis of energy consumption andongoing optimisation.Integrated calendar functionality enables requirement-adapted plantoperation with the lowest possible energy consumption.

Areas of use
Utilisable for various purposes such as fan coil, chill beam control,light control, heat pumps, ventilation systems or roof-top units.

Properties

  • Compact, freely programmable LON automation station
  • Supports LONMARK object types #0, #1, #3, #20020, #3300 and#20100
  • LONMARK certified pursuant to Interoperability DirectiveVersion 3.4
  • Separable lower housing for separate installation ofterminals and electronic components
  • Audio jacks for fast access to the LON network
  • LNS plug in for simple function configuration
  • EY-AS422F002 with manual operating level for switchingbetween manual and automatic operation.


Technical description

  • Voltage supply 24 V~/=
  • Universal inputs and outputs configurable with software
  • 12 universal inputs
  • 12 fused universal outputs
  • 4 scheduler objects
  • 128 k Flash memory for up to 12'000 event entries
  • Real Time Clock
  • TP/FT 10, 78 Kbps
  • Neuron 3150 processor



Short manual(760 KB)